The isolating transducers IM12-AI01-1I-2IUHPR/24VDC/CC transmit analog measured
signals galvanically isolated. The devices are
suitable for operation in zone 2.
The 1-channel device has one input for the
operation of HART® 2-wire transducers as
well as active and passive HART® 2-wire
transmitters. Connection is via removable
spring type terminals. The device can be powered from a power bridge that also transmits a
collective fault signal.
The device is equipped with a 4…20 mA input circuit and two 4…20 mA output circuits
(either as source or sink) or 1…5 V (source).
The input signal at input [I1] is transmitted 1:1
to outputs [O1] and [O2] within a range of 3.8
mA…20.5 mA without interference (splitter operation). In addition, digital signals can also be
transmitted bidirectionally in accordance with
the HART® protocol. Digital HART® signals
are only transmitted to output [O1].
Wire break (
22 mA) in the transducer circuit are output as
current < 3.5 mA/voltage < 0.875 V.
The devices have a green power LED (Pwr).
For each input circuit there is a red status
LED. An error in the input circuit causes the
red LED to flash according to NE44.
The device can be used in safety circuits up to
SIL2 (high and low demand according to IEC
61508) and meets the requirements of NE21.
The device is equipped with removable
spring-type terminals.
■ Splitter function
■ Input circuits monitored for wire break and
short circuit
■ Complete galvanic isolation
■ HART transparent
■ Removable spring type terminals
■ Power bridge (connector incl. in delivery)
■ ATEX use in Zone 2, cUL
■ SIL 2
24